      1. Electrified railway automation series

        Electrified railway automation series

        Views:

        YXVQC-211 integrated control device for wattless voltage
        Scope of application
        The comprehensive automation system in YXSI company with the VQC regulation function, the main transformer tap adjusting and shunt capacitors in integrated control.
        Protection function
        A) tap two transformers and four groups of capacitor switching;
        B automatic recognition of the whole substation operation);
        C automatic optimization control scheme);
        D) can realize the cyclic switching capacitor group.
        The main function parameters
        A) action value
        Setting: voltage 5V~120V, power factor 0~1.000;
        The grade difference: voltage 1V, power factor 0.001;
        Action value accuracy: consistency is not greater than action value of 3%; the average error is less than ± 3%.
        B) action time
        Tuning range: 0~9.99S;
        The grade difference: 1S;
        Action value accuracy: consistency is not greater than action value of 5%; the average error is less than ± 5%.

        YXSB-221 digital transformer protection device
        Scope of application
        YXSB-221 digital regulator protection and control device is applicable to electric power, railway, port of 110KV following various substations, distribution of the pressure regulator, pressure regulator unit is the bay level device.
        Protection function
        A) three segment type composite voltage starting over-current protection function;
        B) two segment zero sequence voltage blocking zero sequence current and zero sequence current and zero sequence over-voltage protection lock;
        C) low frequency protection, low voltage protection function;
        D) over load protection function;
        E) automatic and manual OLTC

        Capacitor protection and control device YXSC-222 digital
        Scope of application
        YXSC-222 digital protection and control device for capacitor, low voltage shunt capacitor is a capacitor unit, the interlayer device.
        Protection function
        A) three segment type over-current protection function can be cast back;
        B) zero sequence overcurrent (or unbalanced current) protection function;
        Zero sequence overvoltage (c) or unbalanced voltage) protection function;
        D) over voltage protection function;
        E) low voltage protection function;
        F) a flow blocking low voltage and no flow blocking over voltage protection function;
        The main function parameters
        Current quick break protection, delay quick break protection, over-current protection, zero sequence overcurrent protection
        A) action value
        Setting range 1 ~ 99.99A
        The grading error 0.01A
        Accuracy consistent action value not greater than action value of 3%; the average error is less than ± 3%
        B) action time
        Setting range 0 ~ 9.99s
        The grade difference of 0.01 s
        Movement time in the action current setting value of 2 times, action time setting is 0.01s, the measured action time is not more than 30ms
        Over voltage protection, low voltage protection
        A) action value
        Tuning range of 5~120V
        The grading error 0.01V
        Accuracy consistent action value not greater than action value of 3%; the average error is less than ± 3%
        B) action time
        Setting range 0 ~ 40.00s
        The grade difference of 0.01 s
        Movement time in the action current setting value of 2 times, action time setting is 0.01s, the measured action time is not more than 30ms

        Self closing line protection and control device YXSL-228 digital link
        Scope of application
        YXSL-228 digital through self closing line protection and control device for railway, autism, autism through variable (with) line substation, line unit of bay level device.
        Protection function
        A) three low voltage blocking direction overcurrent protection;
        B) an automatic reclosing function phase synchronism check and check no pressure;
        C) voltage loss protection function;
        D) from the vote function line;
        E Underfrequency) function;
        F) small current grounding line selection function;
        G) the zero sequence current protection function;
        H) overload.
        The main function parameters
        Quick break protection, delay quick break protection, over-current protection, zero sequence current protection
        A) action value:
        Tuning range of 1 ~ 99.99A; (zero sequence current of 0 ~ 5A)
        The grading error 0.01A
        Accuracy consistent action value not greater than action value of 3%; the average error is less than ± 3%
        B) action time:
        Setting range 0 ~ 9.99s
        The grading error 0.01s
        Action time accuracy in the action current of 2 times the measured action time, consistency is not greater than 20ms, the average error is less than ± 20ms action time
        Alternating direction function
        The sensitive angle -30 ° /-45 ° (optional), the average error is less than ± 5 °, consistency is not greater than 5 deg.
        Action 160 degrees, the average error is less than ± 5 °
        The minimum action power line voltage is 0.5V, the maximum angular sensitivity test is not more than 0.5VA
        Low voltage blocking function
        Tuning range of 5V~100V, the grading 1V, error is less than ± 3%
        Reclosing function
        Protection is a three-phase reclosing function
        Reclosing time delay: setting range 0.1 ~ 9.99s
        The grading error 0.01s
        Accuracy and consistency of action time is not more than 20ms
        The average error less than ± 20ms action
        After acceleration
        Acceleration a, two section, three section is optional after
        Each post acceleration control word alone to cast back
        Post acceleration delay time: setting range 0 ~ 3S
        The grading error 0.01s
        Accuracy and consistency of action time is not more than 20ms
        The average error less than ± 20ms action
        Underfrequency Load Function
        A) carrier frequency underfrequency:
        Tuning range: 46 HZ ~50 Hz
        The grade difference: 0.01 Hz
        Action value accuracy: consistency is not greater than 0.01 Hz; the average error is less than ± 0.02 Hz
        B) low-voltage blocking under frequency load shedding:
        Tuning range: 5V~100V
        The grade difference: 1V
        Action value accuracy: consistency is not greater than action value of 3%, the average error is less than ± 3%
        C low current locking UFLS):
        Tuning range: 0.2~99.99A
        The grade difference: 0.01A
        Action value accuracy: consistency is not greater than action value of 3%, the average error is less than ± 3%
        D) slip blocking of under frequency load shedding:
        Setting: Δ F Δ T 0~10 Hz; fixed tuning of 0.5 s
        The grade difference: F 0.01 Hz
        Action value accuracy: consistency is not greater than 0.02 Hz/ s; the average error is less than ± 0.05 Hz/ s
        E) UFLS action time:
        Setting time: 0.1 ~ 9.99s
        The grade difference: 0.01s
        Action: the accuracy of time consistency is not more than 20ms, the average error is less than ± 20ms action time
        Small current grounding line selection function
        The zero sequence current is not less than 0.02A, the zero sequence voltage is more than 10V, the zero sequence voltage, zero sequence current is applied using the 5 harmonic or harmonic, zero sequence current and zero sequence voltage when the lead between 10 ° ~170 °, convicted of small current grounding, boundary error is less than ± 5 °; sensitive angle +90 °.
        Under voltage protection function, automatic standby line
        A) action value:
        Tuning range of 5~120V
        The grading error 0.01V
        Accuracy consistent action value not greater than action value of 3%; the average error is less than ± 3%
        B) action time:
        Setting range 0.1 ~ 9.99s
        The grade difference of 0.01 s
        Movement time in the action current setting value of 2 times, action time setting is 0.01s, the measured action time is not more than 30ms

        YXSL-226A power line protection device
        Scope of application
        YXSL-226A digital power line protection and control device for electric power, railway, port of 110KV following various substation, power distribution power line, is a line unit of bay level device.
        Protection function
        The three section of low voltage blocking direction overcurrent protection
        A three-phase automatic reclosing function;
        Voltage loss protection function
        Overvoltage protection function
        Underfrequency Load Function
        Small current grounding line selection function
        The zero sequence current protection function
        The main function parameters
        Quick break protection, delay quick break protection, over-current protection, zero sequence current protection
        A) action value
        Tuning range of 1 ~ 99.99A; (zero sequence current of 0 ~ 5A)
        The grading error 0.01A
        Accuracy consistent action value not greater than action value of 3%; the average error is less than ± 3%
        B) action time
        Setting range 0 ~ 9.99s
        The grading error 0.01s
        Action time accuracy in the action current of 2 times the measured action time, consistency is not greater than 20ms, the average error is less than ± 20ms action time
        C) phase to phase function
        The sensitive angle -30 ° /-45 ° (optional), the average error is less than ± 5 °, consistency is not greater than 5 deg.
        Action 160 degrees, the average error is less than ± 5 °
        The minimum action power line voltage is 0.5V, the maximum angular sensitivity test is not more than 0.5VA
        D low voltage blocking) function
        Tuning range of 5V~100V, the grading 1V, error is less than ± 3%
        Reclosing function
        Protection is a three-phase reclosing function
        Reclosing time delay: setting range 0.1 ~ 9.99s
        The grading error 0.01s
        Accuracy and consistency of action time is not more than 20ms
        The average error less than ± 20ms action
        After acceleration
        Acceleration a, two section, three section is optional after
        Each post acceleration control word alone to cast back
        Post acceleration delay time: setting range 0 ~ 3S
        The grading error 0.01s
        Accuracy and consistency of action time is not more than 20ms
        The average error less than ± 20ms action
        Underfrequency Load Function
        A) carrier frequency Underfrequency
        Tuning range: 46 HZ ~50 Hz
        The grade difference: 0.01 Hz
        Action value accuracy: consistency is not greater than 0.01 Hz; the average error is less than ± 0.02 Hz
        B) low-voltage blocking under frequency load shedding
        Tuning range: 5V~100V
        The grade difference: 1V
        Action value accuracy: consistency is not greater than action value of 3%, the average error is less than ± 3%
        C low current locking UFLS)
        Tuning range: 0.2~99.99A
        The grade difference: 0.01A
        Action value accuracy: consistency is not greater than action value of 3%, the average error is less than ± 3%
        D) slip blocking of under frequency load shedding
        Setting: Δ F Δ T 0~10 Hz; fixed tuning of 0.5 s
        The grade difference: F 0.01 Hz
        Action value accuracy: consistency is not greater than 0.02 Hz/ s; the average error is less than ± 0.05 Hz/ s
        E) UFLS action time
        Setting time: 0.1 ~ 9.99s
        The grade difference: 0.01s
        Action: the accuracy of time consistency is not more than 20ms, the average error is less than ± 20ms action time
        Small current grounding line selection function
        The zero sequence current is not less than 0.02A, the zero sequence voltage is more than 10V, the zero sequence voltage, zero sequence current is applied using the 5 harmonic or harmonic, zero sequence current and zero sequence voltage when the lead between 10 ° ~170 °, convicted of small current grounding, boundary error is less than ± 5 °; sensitive angle +90 °.
        Under voltage protection, over-voltage protection function
        A) action value
        Tuning range of 5~120V
        The grading error 0.01V
        Accuracy consistent action value not greater than action value of 3%; the average error is less than ± 3%
        B) action time
        Setting range 0.1 ~ 9.99s
        The grade difference of 0.01 s
        Movement time in the action current setting value of 2 times, action time setting is 0.01s, the measured action time is not more than 30ms